Product Overview

The 3VMS combines the benefits of the ICM450A programmable 3-phase line voltage monitor and a ICM530 type 1 and type 2 three-phase Surge Protective Device into one easy to install solution. The 3VMS protects against both power surges and over/under voltage issues that can cause damage to circuit boards and motors in residential and commercial three-phase 208/240 VAC HVAC/R equipment.

vendor logo
divider
authorized dealer
checkmark

Brand new in box

checkmark

Limited lifetime product warranty

checkmark

Ships from TX

checkmark

Authorized ICM Controls dealer

Features

  • All components are pre-wired for 208/240 volts
  • Modular design with field replaceable components
  • Field programmable voltage monitor with backlit LCD display and a large fault history
  • Protects against over and under voltage, phase loss, phase reversal, phase unbalance and rapid short cycling
  • Separate 40amp contactor, fully disconnects from the service
  • Superior TMOV technology provides safe and reliable surge protection, up to 150 kA max surge event
  • Built to withstand the high impact of a major surge event
  • NEMA type 4X Rating
  • UL Listed: ICM450A UL file number E53944
  • UL Listed: ICM530 UL file number E347279

Specifications

Model 3VMS
Maximum Surge Current 150,000 amps
Protection Modes L-L, L-N (L-N protection available only when Neutral is connected)
User Adjustable Settings
Voltage Set Point 208/240 VAC (do not set above 240VAC)
Delay on Fault 0-15 seconds
Percent Unbalance 2% - 20% (do not set above 10%)
Anti-Short Cycle Time Delay 15 sec to 10 min
Over/Under Voltage Setting 2-25% (do not set above 5% when voltage set point is 240VAC)
Inputs
Line Voltage 208/240 VAC
Frequency 50/60 Hz
Outputs
Type Relay, SPDT
2-Pole Contact Ratings 40A, 208/240 VAC
Dimensions 7.97" x 5.18" x 11.95"

Package Contents

ICM Controls 3VMS 3-Phase Surge Protector and Voltage Monitor

Installation Manual

Warranty

vendor logo
divider
authorized dealer

This item comes with a limited lifetime product warranty.

Manuals & Documentation

Customer Reviews

Customer Reviews

Be the first to write a review
0%
(0)
0%
(0)
0%
(0)
0%
(0)
0%
(0)

Similar Products