(Continuation...) So after 2 hours of figuring out what was going on with the parallel kit, I will try to explain what was going on. I am getting the 50 amps. So in the generator when checking the power output of the 2 normal wall plugs, there is not a standard reading for a house. Normal house wall plugs show a reading of 120 on the left / ground and nothing on the right / ground from what the electrician told me. The generator was showing a reading of 60 on left / ground and 60 on the right / ground. SOOOOO! with the 50 amp parallel kit we could only get 60 on the right and 60 on the left but when combine the right and left you get 120. Maybe this isn't making sense however we did have to rework the box in the trailer since I have a 2 pull 50 amp. We had to put the red and black hots into 1 of the 50 amp slots and jump it to the other. That allows us to get the parallel kit to work normally with the two generators.